80KVA Three Phase DPH Delta UPS

In Stock

KSh 970,000.00

In Stock
Have a Question? Ask a us

+254 (0) 111 053-530 Start Whatsapp Chat

Low Prices

Price match guarantee

Guaranteed Fitment.

Always the genuine part

In-House Experts.

We know our products

Easy Returns.

Quick & Hassle Free

Category:

Description

DPH 80KVA Delta UPS

Model

DPH-120K

Power Rating

120 kW

Power Module Quantity: Up to 6 units

Input

Nominal Voltage

220/380 Vac, 230/400 Vac, 240/415 Vac (3-phase, 4-wire + G)

Voltage Range

305~478 Vac (full load), 228~478 Vac (70% load)

Current Harmonic Distortion

≤ 2%*

Power Factor

> 0.99

Frequency Range

50/60 Hz

Output

Voltage: 220/380 Vac, 230/400 Vac, 240/415 Vac (3-phase, 4-wire + G)

Voltage Harmonic Distortion

≤ 1% (linear load)

≤ 4% (non-linear load)

Voltage Regulation

±1% (static)

Frequency

50/60 Hz

Overload Capability

≤ 125%: 10 minutes

≤ 150%: 1 minute

> 150%: 1 second

Display

10” color touch screen

Interface

Standard

External battery temperature detection x 4, External switch/breaker status dry contact x 4, Output dry contact x 6, Input dry contact x 4, Parallel port x 2, USB Port (Type A x 2, Type B x 1), RS232 Port x 1, Modbus Port x 1, BMS (RJ45) x 1, Ethernet x 1, SNMP Slot x 1, REPO Port x 1

Conformance

Safety

CE

Efficiency

AC-AC

> 96% (Peak efficiency)

ECO Mode

99%

Battery

Nominal Voltage

±240 Vdc (default, ±180~±276 Vdc configurable)

Charge Voltage

±272 Vdc (adjustable from 204 to 312 V)

Protection of Battery Deep Discharge

Yes

Environment

Operating Temperature

0~40℃

Relative Humidity

95% (non-condensing)

Audible Noise (at one meter)

< 65 dB

IP Protection

IP20

Others

Parallel Redundancy and Expansion

Module and system redundancy, Maximum 8 units

Battery Start

Yes

Physical

Dimensions (W x D x H)

600 x 850 x 1445 mm

Weight

162 kg

Weight – 20 kW Power Module (optional)

18 kg

DPH 80KVA Delta UPS Documents