20KVA Delta HPH 20KVA I/O=230/400V Delta UPS (No Battery)
KSh 650,000.00
+254 (0) 111 053-530 Start Whatsapp Chat
Description
HPH 20KVA I/O=230/400V Delta UPS (No Battery)
Model
Long backup model
HPH-20KVA
Inbuilt battery model – no batteries inside
Power Rating
20 kVA / 20 Kw
Input
Nominal Voltage: 220/380 Vac, 230/400 Vac, 240/415 Vac (3-phase, 4-wire + G)
Voltage Range: 305~478 Vac (full load)
Current Harmonic Distortion: ≤ 2.5%
Power Factor: > 0.99
Frequency Range: 40~70 Hz
Output
Voltage: 220/380 Vac, 230/400 Vac, 240/415 Vac (3-phase, 4-wire + G)
Voltage Harmonic Distortion
≤ 1.5% (linear load)
≤ 4% (non-linear load)
Voltage Regulation: ± 1% (static)
Frequency: 50/60 Hz
Overload Capability
≤ 105%: continuously
> 105~≤ 110%: 60 minutes
> 110~≤ 125%: 10 minutes
> 125~≤ 150%: 1 minute
> 150%: 1 second
Display
5” color touch screen
Interface
Standard
External battery temperature detection x1, Output dry contact x4, Input dry contact x2, Parallel port x2, USB Port x1, RS232 Port x1, REPO Port x1, Mini Slot x2
Conformance
Safety: CE, RCM (IEC62040-1, IEC62040-2 Class C2)
Efficiency
AC-AC: > 96% (Peak efficiency)
ECO Mode: 99%
Battery
Nominal Voltage: ± 240 Vdc (default, ± 180 Vdc~± 276 Vdc configurable)
Charge Voltage: ± 272 Vdc (adjustable from 204 V to 312 V)
Maximum Inbuilt Charger Current: 15 A
Discharge Time: 20 minutes
Environment
Operating Temperature: 0~40℃
Relative Humidity: 0~95% (non-condensing)
Audible Noise (at one meter): < 50 dB
IP Protection: IP20 (Standard)
IP42 (Optional for long backup model)
Others
Parallel Redundancy and Expansion: Up to 4 units
Battery Start: Yes
Physical
Dimensions (W x D x H): 240 x 630 x 650 mm
Weight
44 kg
Physical (HPH-B/B-N)
Dimensions (W x D x H): 410 x 780 x 1200 mm
HPH 20KVA Documents